Chapter 11 Summary of Parameter SettingsCFP2000 Series
11-31
10 Speed Feedback Control Parameters
NOTE
IM: Induction Motor; PM: Permanent Magnet Motor
Pr.
Explanation
Settings
Factory
Setting
10-00
~
10-30
Reserved
10-31
I/F Mode, current command
0~150%Irated (Rated current % of motor)
40
10-32
PM Sensorless Observer
Bandwidth for High Speed Zone
0.00~599.00Hz
5.00
10-33
Reserved
10-34
PM Sensorless Observer
Low-pass Filter Gain
0.00~655.35
1.00
10-35
~
10-38
Reserved
10-39
Frequency when switch from I/F
Mode to PM sensorless mode.
0.00~599.00Hz
20.00
10-40
Frequency when switch from I/F
sensorless observer mode to
V/F mode.
0.00~599.00Hz
20.00
10-41
I/F mode, low pass-filter time
0.0~6.0sec
0.2
10-42
Initial Angle Detection Time
0.0~3.0
1.0
10-43
~
10-48
Reserved
10-49
Zero voltage time while start up
0.000~60.000 sec
00.000
10-50
Reserved
10-51
Injection Frequency
0~1200Hz
500
10-52
Injection Magnitude
0.0~200.0V
15.0/30.0
10-53
PM motor rotor initial angle
position detection method
0: Disable
1: Internal 1/4 rated current attracting the rotor to zero
degrees
2: High frequency injection
3: Pulse injection
4~5: Reserved
0