Chapter 11 Summary of Parameter SettingsCFP2000 Series
11-33
12 Pump Parameters
Pr.
Explanation
Settings
Factory
Setting
12-00
Circulative Control
0: No operation
1: Fixed Time Circulation (by time)
2: Fixed quantity circulation (by PID)
3: Fixed quantity control
4: Fixed Time Circulation+ Fixed quantity circulation
5: Fixed Time Circulation+ Fixed quantity control
0
12-01
Number of motors to be
connected
From only 1 and up to 8 motors
1
12-02
Operating time of each motor
(minutes)
0 to 65500 min
0
12-03
Delay Time due to the
Acceleration (or the Increment )
at Motor Switching
0.0 to 3600.0 sec
1.0
12-04
Delay Time due to the
Deceleration ( or the Decrement)
at Motor Switching (seconds)
0.0 to 3600.0 sec
1.0
12-05
Delay time while fixed quantity
circulation at Motor Switching
(seconds)
0.0 to 3600.0 sec
10.0
12-06
Frequency when switching
motors at fixed quantity
circulation (Hz)
0.00 to 599.00 Hz
60.00
12-07
Action to do when Fixed
Quantity Circulation breaks
down.
0: Turn off all output
1: Motors powered by mains electricity continues to
operate.
0
12-08
Frequency when stopping
auxiliary motor (Hz)
0.00 to 599.00 Hz
0.00