Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-00-8
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (no CANopen card)
It is used to set the source of the master frequency in AUTO mode.
Pr.00-20 and 00-21 are for the settings of frequency source and operation source in AUTO mode.
Pr.00-30 and 00-31 are for the settings of frequency source and operation source in HAND mode.
The AUTO/HAND mode can be switched by the keypad KPC-CC02 or multi-function input
terminal (MI).
The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal
used to switch AUTO/HAND mode. The highest priority is the multi-function input terminal. When
the external terminal is OFF, the drive won’t receive any operation signal and can’t execute JOG.
Source of the Operation Command (AUTO)
Factory Setting: 0
Settings 0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen card
5: Communication card (not includes CANopen card)
It is used to set the source of the operation frequency in AUTO mode.
When the operation command is controlled by the keypad KPC-CC02, keys RUN, STOP and
JOG (F1) are valid.
Stop Method
Factory Setting: 0
Settings 0: Ramp to stop
1: Coast to stop
The parameter determines how the motor is stopped when the AC motor drive receives a valid
stop command.
Ramp to Stop and Coast to Stop
Operation
Command
Motor
Rotation
Speed
Oper ation
Command
Frequency
Time
Time
Stops according to
deceleration time
Free running
to stop
Output
Frequency
RUN
ST O P
RUN
STO P
Motor
Rotation
Speed
Frequenc