Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-01-7
01-00
01-13,15,17,19,21
01-12,14,16,18,20
Frequency
Time
Max. Output
Frequency
Frequency
Setting
accel. time decel. time
Accel./Decel. Time
JOG Frequency
Factory Setting: 6.00
Settings 0.00~599.00Hz
Both external terminal JOG and key “F1” on the keypad KPC-CC01 can be used. When the jog
command is ON, the AC motor drive will accelerate from 0Hz to jog frequency (Pr.01-22). When
the jog command is OFF, the AC motor drive will decelerate from Jog Frequency to zero. The Jog
Accel./Decel. time (Pr.01-20, Pr.01-21) is the time that accelerates from 0.0Hz to Pr.01-22 JOG
Frequency.
The JOG command can’t be executed when the AC motor drive is running. In the same way,
when the JOG command is executing, other operation commands are invalid.
It does not support JOG function in the optional keypad KPC-CC02.
1st/4th Accel./decel. Frequency
Factory Setting: 0.00
Settings 0.00~599.00Hz
The transition from acceleration/deceleration time 1 to acceleration/deceleration time 4, may also
be enabled by the external terminals. The external terminal has priority over Pr. 01-23.
When using this function, please set S-curve acceleration time as 0 if 4
th
acceleration time is set
too short.
Fr
e
q
u
e
nc
y
Time
01-23
4t h A c cele ra t io n
Time
4th Deceleration
Time
1s t Accel era tion
Ti me
1st Deceleration
Time
1st/4th Acceleration/Deceleration Frequency Switching