Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-01-9
0
01-28
01-29
01-30
01-31
01-32
01-33
Internal
frequency
command
Frequency setting command
rising frequency
fa ll ing fr equency
Zero-speed Mode
Factory Setting: 0
Settings 0: Output waiting
1: Zero-speed operation
2: Fmin (Refer to Pr.01-07, 01-41)
When the frequency is less than Fmin (Pr.01-07 or Pr.01-41), it will operate by this parameter.
When it is set to 0, the AC motor drive will be in waiting mode without voltage output from
terminals U/V/W.
When setting 1, it will execute DC brake by Vmin(Pr.01-08 and Pr.01-42) in V/f, and SVC modes.
When it is set to 2, the AC motor drive will run by Fmin (Pr.01-07, Pr.01-41) and Vmin (Pr.01-08,
Pr.01-42) in V/F, SVC modes.
In V/F, SVC modes
fmin
01-07
fou
t
0Hz
01-34=0
01-34=2
01-34=1
0Hz
stop output
0Hz operation
(DC brake)
stop waiting for output
In FOCPG mode, when Pr.01-34 is set to 2, it will act according Pr.01-34 setting.
fmin
01-07
fout
01-34=0
01-34=2
01-34=1
frequency command
frequency command
V/F Curve Selection
Factory Setting: 0
Settings
0~15
V/F curve can be selected from 15 kinds of default settings or set manually.
Different kinds of V/F curves are shown in the table below. There are 15 kinds of V/F curve to be