Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-06-24
Fire Mode
Factory Setting: 0.00
Settings 0: No Function
1: Forward Operation
2: Reverse Operation
This parameter needs to work with multi-input function terminal #58 or #59 and multi-output
function terminal #53 and #54.
Setting is 0: Fire mode is disabled
Setting is 1: When there is a fire, motors will operate clockwisely (U, V.W).
Setting is 2: When there is a fire, motors will operate counter-clockwisely.
Operating Frequency when running Fire Mode
Factory Setting: 60.00
Settings 0.00 ~ 599.00 Hz
This parameter is to set up the drive’s frequency when the fire mode is enabled.
Enable Bypass on Fire Mode
Factory Setting: 0.
Settings 0: Disable Bypass
1: Enable Bypass
Bypass Delay Time on Fire Mode
Factory Setting: 0.0
Settings 0.00 ~ 6550.0 seconds
Number of Times of Unusual Reset at Fire Mode
Factory Setting: 0
Settings 0 ~ 10
Length of Time of Unusual Reset
Factory Setting: 60.0
Settings 0.00 ~ 6000.0sec
The settings of Pr.06-82 to Pr.06-85 decide if switch motors to operating under mains electricity.
Diagram of Bypass function’s Sequence