Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-07-4
Time
B.B.
output current A
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
Speed Search
Synchronization speed detection
Output frequency
(H)
07-09 Current Limit
for Speed Search Speed
FWD Run
B.B. Search with minimum output frequency upward timing chart
Output voltage
(V)
B.B. Search with minimum output frequency upward timing chart
Output frequency(H)
Output voltage(V)
Output current
06-03
Over-Current Stall
Prevention
during Accel.
FWD Run
Time
Input B.B. signal
Stop voltage output
Disable B.B. signal
Waiting time Pr.07-08
Speed search
Synchronization speed detection
B.B.
A
Current Limit for Speed Search
Factory Setting: 100
Settings 20~200%
Following a momentary power loss, the AC motor drive will start its speed search operation only
if the output current is greater than the value set by Pr.07-09.
When executing speed search, the V/f curve is operated by group 1 setting. The maximum
current for the optimum accel./decel. and start speed search is set by Pr.07-09.
The maximum speed search level will affect the synchronous time. It will get the synchronization
faster when this parameter is set to larger value. But too large value may activate overload
protection.
Treatment after Fault
Factory Setting: 0
Settings 0: Stop operation
1: Speed search starts with current speed
2: Speed search starts with minimum output frequency
Fault includes: bb,oc,ov,occ. To restart after oc, ov, occ, Pr.07-11 can not be set to 0.