EasyManua.ls Logo

Delta VFD007FP4EA-41 - Page 343

Delta VFD007FP4EA-41
404 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-09-1
09 Communication Parameters The parameter can be set during the operation.
Pin 1~2,7,8: Reserved
Pin 3, 6: GND
Pin 4: SG-
Pin 5: SG+
RS-485
8
1
Modbus RS-485
When using communication devices,
connects AC drive with PC by using
Delta IFD6530 or IFD6500.
COM1 Communication Address
Factory Setting: 1
Settings 1~254
If the AC motor drive is controlled by RS-485 serial communication, the communication address
for this drive must be set via this parameter and each AC motor drive’s communication address
must be different.
COM1 Transmission Speed
Factory Setting: 9.6
Settings 4.8~115.2Kbits/s
This parameter is for set up the RS485 communication transmission speed.
COM1 Transmission Fault Treatment
Factory Setting: 3
Settings
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
This parameter is to set the reaction of MODBUS transmission errors with the host. Detection
time can be set in Pr09-03.
COM1 Time-out Detection
Factory Setting: 0.0
Settings 0.0~100.0 sec
0.0: Disable
It is used to set the communication transmission time-out.
COM1 Communication Protocol
Factory Setting: 1
Settings 1: 7, N, 2 for ASCII
2: 7, E, 1 for ASCII
3: 7, O, 1 for ASCII
4: 7, E, 2 for ASCII
5: 7, O, 2 for ASCII
6: 8, N, 1 for ASCII
7: 8, N, 2 for ASCII
8: 8, E, 1 for ASCII

Table of Contents