Chapter 7 Optional Accessories |CFP2000 Series 
 
 
7-10
The suggested motor shielded cable length in the following table complies with IEC 60034-17, which is 
suitable for motors with a rated voltage ≤500 Vac and with an insulation level of ≥1.35 kVp-p   
 
Type kW  HP 
Rated Amps of AC Reacto
shielded cable 
(meter) 
Non-shielded 
cable (meter) 
007 0.75  1  2.8  3  50  75  75  115 
015 1.5  2  3  4.2  50  75  75  115 
022 2.2  3  4  5.5  50  75  75  115 
037 3.7  5  6  8.5  50  75  75  115 
040 4  5  9  10.5  50  75  75  115 
055 5.5 7.5  10.5  13  50  75  75  115 
075 7.5  10  12  18  100  150  150  225 
110 11  15  18  24  100  150  150  225 
150 15  20  24  32  100  150  150  225 
185 18.5  25  32  38  100  150  150  225 
220 22  30  38  45  100  150  150  225 
300 30  40  45  60  100  150  150  225 
370 37  50  60  73  100  150  150  225 
450 45  60  73  91  150  225  225  325 
550 55  75  91  110  150  225  225  325 
750 75 100 110 150 150  225  225 325 
900 90 125 150 180 150  225  225 325