Chapter 7 Optional Accessories |CFP2000 Series
7-10
The suggested motor shielded cable length in the following table complies with IEC 60034-17, which is
suitable for motors with a rated voltage 500 Vac and with an insulation level of 1.35 kVp-p
Type kW HP
Rated Amps of AC Reacto
r
(Arms)
Without installation AC output Reactor 3% Output AC reactor
Normal Duty
Light Duty shielded cable (meter)
Non-shielded cable (meter)
shielded cable
(meter)
Non-shielded
cable (meter)
007 0.75 1 2.8 3 50 75 75 115
015 1.5 2 3 4.2 50 75 75 115
022 2.2 3 4 5.5 50 75 75 115
037 3.7 5 6 8.5 50 75 75 115
040 4 5 9 10.5 50 75 75 115
055 5.5 7.5 10.5 13 50 75 75 115
075 7.5 10 12 18 100 150 150 225
110 11 15 18 24 100 150 150 225
150 15 20 24 32 100 150 150 225
185 18.5 25 32 38 100 150 150 225
220 22 30 38 45 100 150 150 225
300 30 40 45 60 100 150 150 225
370 37 50 60 73 100 150 150 225
450 45 60 73 91 150 225 225 325
550 55 75 91 110 150 225 225 325
750 75 100 110 150 150 225 225 325
900 90 125 150 180 150 225 225 325