Chapter 11 Summary of Parameter SettingsMS300 (High Speed Model)
11-18
05 Motor Parameters
Pr. Explanation Settings
Factory
Setting
05-01
Full-load current of induction
motor 1 (A)
10~120 % of drive’s rated current #.##
05-02
Rated power of induction motor 1
(kW)
0~655.35 kW #.##
05-03
Rated speed of induction motor 1
(rpm)
0~65535
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
1710
05-04 Pole number of induction motor 1 2~20 4
05-13
Full-load current of induction
motor 2 (A)
10~120 % of drive’s rated current
#.##
05-14
Rated power of induction motor 2
(kW)
0~655.35 kW
#.##
05-15
Rated speed of induction motor 2
(rpm)
0~65535
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
1710
05-16
Pole number of induction motor 2 2~20 4
05-17
No-load current of induction
motor 2 (A)
0~ Pr. 05-13 factory setting
#.##
05-22 Multi-motors (induction) selection
1: Motor 1
2: Motor 2
3: Motor 3
4: Motor 4
1
05-23
Frequency for Y-connection
/-connection switch of induction
motor
0.0~1500.0 Hz
600.0
05-24
Y-connection /-connection
switch of induction motor
0: Disable
1: Enable
0
05-25
Delay time for Y-connection
/-connection switch of induction
motor
0.000~60.000 sec.
0.200
05-26
Accumulative Watt-second of
motor in low word (W-sec)
Read only
#.#
05-27
Accumulative Watt-second of
motor in high word (W-sec)
Read only
#.#
05-28
Accumulative Watt-hour of motor
(W-Hour)
Read only
#.#
05-29
Accumulative Watt-hour of motor
in low word (KW-Hour)
Read only
#.#
05-30
Accumulative Watt-hour of motor
in high word (KW-Hour)
Read only
#.#