Chapter 16 PLC Function ApplicationsMS300 (High Speed Model)
16-89
API
OR#
S1 S2
Contact form logical operation OR#
221~
223
D
Bit device Word device
16-bit command (5 STEP)
OR# Continuous
execution type
32-bit command (9 STEP)
DOR# Continuous
execution type
Flag signal: none
X Y M K H KnX KnY KnM T C D
S1
S2
Notes on operand usage: #:&|^
Please refer to the function specifications table for each device in
series for the scope of device usage
S
1
: data source device 1. S
2
: data source device 2.
This command performs comparison of the content of S
1
and S
2
; when the result
of comparison is not 0, this command will be activated, but this command will not
be activated when the result of comparison is 0.
The OR# command is an operation command in series with the contact.
API No.
16-bit
commands
32-bit
commands
Conditions for
activation
Conditions for inactivation
221 OR&
DOR&
S
1
&
S
2
0
S
1
&
S
2
0
222 OR| DOR|
S
1
|
S
2
0
S
1
|
S
2
0
223 OR^ DOR^
S
1
^
S
2
0
S
1
^
S
2
0
  &: logical AND operation.
  |: logical OR operation.
  ^: logical XOR operation.
When X1=On or the content of C0 and C10 is subjected to the logical
AND operation, and the result is not equal to 0, Y0=On.
When X2 and M30 are both equal to On, or the content of 32-bit register D10
(D11) and 32-bit register D20 (D21) is subjected to the logical OR operation, and
the result is not equal to 0, or the content of the 32-bit counter C235 and the 32-bit
register D200 (D201) is subjected to the logical XOR operation, and the result is
not equal to 0, M60=On.
OR
C0 C10
DOR
D10 D20
&
I
Y0
X2
X1
M30
M60
DOR
D25
D200
^