Chapter 16 PLC Function ApplicationsMS300 (High Speed Model)
16-91
API
AND
S1 S2
Contact form compare AND*
232~
238
D
Bit device Word device
16-bit command (5 STEP)
AND
Continuous
execution type
32-bit command (9 STEP)
DAND
Continuous
execution type
Flag signal: none
X Y M K H KnX KnY KnM T C D
S1
S2
Notes on operand usage: =><<>
Please refer to the function specifications table for each device in
series for the scope of device usage
S
1
: data source device 1. S
2
: data source device 2.
This command compares the content of S
1
and S
2
. Taking API 232 (AND=) as an
example, when the result of comparison is equal, this command will be activated;
when the result of comparison is unequal, this command will not be activated.
The AND* command is a comparison command in series with a contact.
API No. 16-bit commands 32-bit commands
Conditions for
activation
Conditions for
inactivation
232
AND DAND
S
1
S
2
S
1
S
2
233
AND DAND
S
1
S
2
S
1
S
2
234
AND DAND
S
1
S
2
S
1
S
2
236
AND<> DAND<>
S
1
S
2
S
1
S
2
237
AND<= DAND<=
S
1
S
2
S
1
S
2
238
AND>= DAND>=
S
1
S
2
S
1
S
2
When X0=On and the current value of C10 is also equal to K200, Y10=On.
When X1=Off and the content of register D0 is not equal to K-10, Y11=On and
remains in that state.
When X2 =On and the content of the 32-bit register D0(D11)is less than 678,493,
or M3=On, M50=On.
AND=
K200 C10
DAND>
K678493 D10
M3
Y10
AND<>
K-10 D0
SET Y11
M50
X2
X1
X0