EasyManua.ls Logo

Det-Tronics X3302 - False Alarm Response

Det-Tronics X3302
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29 95-87682.1
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES
Very High Sensitivity
False Alarm Source
Distance
to source
feet (m)
Fire source and size/
ow rate
Distance to
fire feet (m)
Average
Response time
(seconds)**
Sunlight, direct, unmodulated*
Hydrogen @ 100 SLPM 125 (38.1)
2.6
Sunlight, direct, modulated*
Hydrogen @ 25 SLPM 10 (3.0)
7.0
Sunlight, reflected, unmodulated*
Hydrogen @ 100 SLPM 125 (38.1)
2.6
Sunlight, reflected, modulated*
Hydrogen @ 100 SLPM 60 (18.2)
2.1
Arc welding, unmodulated
30 (9.1) Hydrogen @ 100 SLPM 125 (38.1)
3.8
Arc welding, modulated 40 (12.2) Hydrogen @ 100 SLPM
125 (38.1) 4.6
70 W sodium vapor lamp, unmodulated 10 (3.0)
Hydrogen @ 100
SLPM
125 (38.1) 2.4
70 W sodium vapor lamp, modulated
10 (3.0)
Hydrogen @ 100
SLPM
125 (38.1) 2.3
250 W mercury vapor lamp, unmodulated 10 (3.0)
Hydrogen @ 100
SLPM
125 (38.1) 2.4
250 W mercury vapor lamp, modulated 10 (3.0)
Hydrogen @ 100
SLPM 125 (38.1)
2.1
300 W clear incandescent lamp, unmodulated 10 (3.0)
Hydrogen @ 100
SLPM
125 (38.1) 1.4
300 W clear incandescent lamp, modulated
10 (3.0)
Hydrogen @ 100
SLPM 125 (38.1)
2.3
500 W shielded quartz halogen lamp, unmodulated 15 (4.6)
Hydrogen @ 100
SLPM
125 (38.1) 1.7
500 W shielded quartz halogen lamp, modulated 15 (4.6)
Hydrogen @ 100
SLPM 125 (38.1)
4.7
1500 W electric quartz heater, unmodulated
15 (4.6)
Hydrogen @ 100
SLPM
125 (38.1) 2.7
1500 W electric quartz heater, modulated 15 (4.6)
Hydrogen @ 100
SLPM
125 (38.1) 3.1
Two 34 W fluorescent lamps, unmodulated 5 (1.5)
Hydrogen @ 100
SLPM
125 (38.1) 2.7
Two 34 W fluorescent lamps, modulated 5 (1.5)
Hydrogen @ 100
SLPM
125 (38.1) 2.2
4000K, 8000 Lumen LED Lamp, unmodulated 5 (1.5)
Hydrogen @ 100
SLPM
125 (38.1) 1.9
4000K, 8000 Lumen LED Lamp, modulated 5 (1.5)
Hydrogen @ 100
SLPM
125 (38.1) 2.2
* Outdoor test conditions.
** Add 2 seconds for EQP model.
High Sensitivity
False Alarm Source
Distance to
source feet (m)
Fire source and size/
ow rate
Distance to
re feet (m)
Average
Response time
(seconds)**
Sunlight, direct, unmodulated*
Hydrogen @ 100 SLPM 110 (33.5)
1.8
Sunlight, direct, modulated*
Hydrogen @ 50 SLPM 10 (3.0)
3.2
Sunlight, reflected, unmodulated*
Hydrogen @ 100 SLPM 110 (33.5)
2.8
Sunlight, reflected, modulated*
Hydrogen @ 100 SLPM 60 (18.3)
3.2
Arc welding, unmodulated 25 (7.6) Hydrogen @ 100 SLPM 110 (33.5)
8.5
Arc welding, modulated 35 (10.7) Hydrogen @ 100 SLPM
110 (33.5) 5.8
70 W sodium vapor lamp, unmodulated 8 (2.4)
Hydrogen @ 100
SLPM
110 (33.5) 2.2
70 W sodium vapor lamp, modulated 8 (2.4)
Hydrogen @ 100
SLPM
110 (33.5) 2.1
250 W mercury vapor lamp, unmodulated 8 (2.4)
Hydrogen @ 100
SLPM
110 (33.5) 2.1
250 W mercury vapor lamp, modulated
8 (2.4)
Hydrogen @ 100
SLPM 110 (33.5)
2.1
300 W clear incandescent lamp, unmodulated 8 (2.4)
Hydrogen @ 100
SLPM
110 (33.5) 2.6
300 W clear incandescent lamp, modulated 8 (2.4)
Hydrogen @ 100
SLPM 110 (33.5)
2.1
500 W shielded quartz halogen lamp, unmodulated 12 (3.7)
Hydrogen @ 100
SLPM
110 (33.5) 2.4
500 W shielded quartz halogen lamp, modulated 12 (3.7)
Hydrogen @ 100
SLPM 110 (33.5)
4.7
1500 W electric quartz heater, unmodulated 14 (4.3)
Hydrogen @ 100
SLPM
110 (33.5) 2.2
1500 W electric quartz heater, modulated 14 (4.3)
Hydrogen @ 100
SLPM 110 (33.5)
2.5
Two 34 W fluorescent lamps, unmodulated 4 (1.2)
Hydrogen @ 100
SLPM
110 (33.5) 2.7
Two 34 W fluorescent lamps, modulated 4 (1.2)
Hydrogen @ 100
SLPM
110 (33.5) 2.0
4000K, 8000 Lumen LED Lamp, unmodulated 4 (1.2)
Hydrogen @ 100
SLPM
110 (33.5) 2.0
4000K, 8000 Lumen LED Lamp, modulated 4 (1.2)
Hydrogen @ 100
SLPM
110 (33.5) 1.4
* Outdoor test conditions.
** Add 2 seconds for EQP model.