For destination countries where CE requirements must be met, individual 400V supply
disconnecting devices for each washer are required and must be one of the following types:
a. switch-disconnector with fuses per IEC 60947-3 utilization category AC-23B;
b. disconnector with fuses per IEC 60947-3 having an auxiliary contact that in all cases causes
switching devices to break the load circuit before the opening of the main contacts of the
disconnector;
c. a circuit-breaker suitable for isolation per IEC 60947-2;
d. any other switching device in accordance with an IEC product standard for that device and
which meets the isolation requirements of IEC 60947-1 as well as a utilization category
defined in the product standard as appropriate for on-load switching of motors or other
inductive loads;
The supply disconnecting devices must
a. provide a direct opening means allowing the supply disconnecting devices to be locked in
the OFF position;
b. have an operating means w/ an OFF and ON position marked with an “O” and “I”
c. be visible and mounted 0.7 m to 1.7 m above the floor, within 2 m from the washer, and
within 8 m from the operator position;
d. have a red actuator with a yellow background to indicate that it serves a dual Emergency
Stop function, and be approved to 60947-5-5 series and for use in the country where
installed;
e. be rated for branch circuit operation;
f. have a break capacity equal to the sum of the largest stalled motor and all other normal
operating loads