EN-18 452172.66.10-EN · FD 0311 www.dimplex.de
English LIA 0608BWCF M - LIA 1316BWCF M
º
If the indoor unit is mounted 4 m or more metres higher or
lower than the outdoor unit, a cooling technology specialist
must perform a separate check to ensure that the devices for
conveying the oil up and down the pipes have been installed
correctly in the split line.
º
The rated output of the device may vary depending on the
split line length.
!
Incorrect filling with refrigerant could lead to faults during
operation.
1) Production operation (see model name label)
2) Installation operation (where possible, attach alongside the
maintenance connections for adding or removing refriger-
ant)
3) Total filling (1, + 2,)
!
If the filling quantity changes, document it in an easily visible
place (e.g. filling quantity on the type plate). Do not add more
than the specified amount of refrigerant to the system.
7.1.2 Preparation for pipework
The preparation of the pipework takes place in five steps. One
main cause of refrigerant leaks is incorrect flanging. Flanging
must be carried out carefully and according to the following
steps.
Step 1: Cutting pipes and cables
Use the installation kit for pipework or the pipes purchased
from your local dealer.
Measure the distance between the indoor and outdoor
unit.
Cut the pipes slightly longer than the measured distance.
Step 2: Removing burrs
Remove all burrs from the interface of the pipework.
Hold the pipe end downwards so that no burrs can fall into
the pipe.
Step 3: Inserting screw nuts
Remove the screw nuts on the outdoor unit.
Insert the screw nuts into the deburred pipe.
No nuts can be inserted into the pipe after flanging.
Step 4: Flanging
Flanging must be carried out as follows with a flanging tool
for R32 refrigerant as shown in the figure.
&RSSHUSLSH
90q
Tilted Uneven Raw
3LSH
Reamer
Hold facing
downwards
5DLO
Copper pipe
Clamp
Red arrow marking
Cone
Bracket
Handle
Rail
"A"