EN-17
Configuring the Heat Pump Heating System 6.1
English


Sets the desired domestic hot water
temperature which is to be reached in parallel
operation.
30 °C
... 60 °C ...
85 °C
Additional HE
Hot water
Sensor


Sets whether the existing flange heater is also
to be used for reheating. If set to “No”, domestic
hot water is only heated up to the current HP
maximum temperature (depending on the heat
source temperature).
No
Yes
Domestic hot water
Flange heater


Sets the time programs for hot water blocks Domestic hot water



Sets the times in which domestic hot water
preparation is blocked.
00:00
...
23:59
Domestic hot water


For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active for a block. Blocks that exceed
a weekday are activated or deactivated at the
end of each day accordingly.
N
T1
T2
Y
Domestic hot water

To carry out a thermal disinfection, the
domestic hot water is heated up once to the
desired temperature. The heating period is
terminated automatically when the set
temperature is reached, at 12:00 p.m. or after 4
hours at the latest.
Hot water
Sensor
Bivalent or flange
heater


Sets the start time for the thermal disinfection 00:00
...
23:59
Hot water
Sensor
Bivalent or flange
heater


Sets the desired hot water temperature which is
to be reached during thermal disinfection
60 °C
... 65 °C ...
85 °C
Hot water
Sensor
Bivalent or flange
heater


For each day of the week, it is possible to select
whether thermal disinfection is desired at the
set start time.
N
Y
Hot water
Sensor
Bivalent or flange
heater


The circulation pump is started using a paddle
flow switch, for example. When the paddle flow
switch returns to the original position, the
circulation pump operates for the duration of
the set time.
1 min
... 5 ...
15 min
Circulation
Pulse


The circulation pump is controlled by a timer
function.
Circulation
Time



Sets the times at which the circulation pump is
to be activated.
00:00
23:59
Circulation
Time


For each day of the week, it is possible to select
whether the circulation pump is activated at the
set start time.
N
Y
Circulation
Time


By setting Reset to “Yes”, the maximum
calculated domestic hot water temperatures in
HP operation are reset to a value of 65 °C. The
setting is automatically reset to “No”.
No
Yes
Hot water
Sensor

System-specific parameters Setting range Display