EN-22
6.4
English


By activating this function, the circulation pump is
switched on constantly for a period of 24 hours.
The heat pump remains blocked during this period.
No
Yes
Circulation

Automatic program for targeted heat drying of
screed floors
Always


Sets the maximum return flow temperature to be
reached during initial heating.
25 °C
... 35 °C ...
50 °C
Always


Selecting this function will permit any request for
domestic hot water or swimming pool water during
initial heating.
No
Yes
Always

Activates the initial heating program. No
Yes
Always


Activates the standard program for screed drying. No
Yes
Always


Sets the duration of the individual steps during the
heating-up phase.
1
... 24...
120
Always


Sets the maintaining time. 1
... 24...
480
Always


Sets the duration of the individual steps during the
heating-down phase.
1
... 24...
120
Always


Sets the temperature difference between the two
steps in the heating-up phase.
1K
... 5K...
10K
Always


Sets the temperature difference between the two
steps in the heating-down phase.
1K
... 5K...
10K
Always


Activates the individual program for screed drying. No
Yes
Always

Function for the heating technician Always
