7.6.1 Additional BA level parameters that can be configured
(available with
enabled)
Display Description
DT - Adjustment of obstacle recognition time. [s/100]
10 - Minimum
60 - Maximum
N.B.: the parameter is adjusted in hundredths of a
second.
40
MP - Start at maximum power
ON - During start-up it increases the thrust on obsta-
cles to maximum.
OFF - During start-up the thrust on obstacles is that
adjusted by -
ST - Adjustment of start time. [s]
0.5 - Minimum
3.0 - Maximum
Neos Super fast
1,0 -
Minimum
4,0 - Maximum
2.0
Neos Super Fast
3.0
TA - Adjustment of acceleration time. [s]
(start speed is 75% of - )
0.5 - Minimum
2.0 - Maximum
Neos Super fast
1,0 -
Minimum
4,0 -
Maximum
1.5
Neos Super Fast
3.0
TD - Adjustment of deceleration time. [%]
10 - Minimum
99 - Maximum
75
OB - Adjustment of deceleration distance during
opening. [cm]
Indicates the distance from the end of the opening
stroke where the deceleration ramp begins.
05 - Minimum
99 - Maximum
N.B.: reduce the deceleration space if there is a series
of quick vibrations (chattering) in heavy gates installed
with a slight incline.
40
Neos Super Fast
99
BA