EasyManua.ls Logo

dixell XC660D - Page 55

dixell XC660D
55 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592001850 XC660D GB r3.4 04.09.2017.docx XC660D 55/55
Label
Valori
Menù
Descrizione Parametri
Limiti
dSES
35.0
Pr2
External temperature set for DYNAMIC SET
POINT function
-50.0 ÷ 150.0 (°C) -58 ÷ 302 (°F)
dSEb
-20.0
Pr2
Proportional band DYNAMIC SET POINT
-50.0 ÷ 50.0(°C) -90 ÷ 90 (°F)
dSEd
5.0
Pr2
Differential for DYNAMIC SET POINT
-50.0÷50.0(°C) -90÷90(°F)
-20.0÷20.0(BAR) -300÷300(PSI)
-2000÷2000(KPA)
AOC
Cur
Pr2
Analogue output 1 working mode
Cur tEn
AOF
nu
Pr2
Analog output 1 function
nu InC1 InC2 InF
InCP
no
Pr2
Frequency compressor always starts at first
no yES
AOP
nP
Pr2
Reference probe for the analog output 1
nP(0) - P3(1) - P4(2)
LAO
0
Pr2
Temperature value associated to minimum
value of analog output (AOM)
-50.0÷150.0(°C) -58÷302(°F)
UAO
100
Pr2
Temperature value associated to the
maximum value of analog output, 10V or
20mA
-50.0÷150.0(°C) -58÷302(°F)
AOM
0
Pr2
Minimum value of analogue output 1
0 ÷ 100 (%)
AOt
0
Pr2
Time with analog output 1 at max when after
exceeding AOM
0÷15s
MPM
100
Pr2
Maximum % variation per minute, analog
output 1
nu, 1 ÷ 100%
SAO
50
Pr2
Percentage of analog output 1 in case of
probe failure
0 ÷ 100 (%)
AOH
70
Pr2
Maximum analog output 1 percentage when
silence mode function is enabled
0 ÷ 100 (%)
2AOC
Cur
Pr2
Analogue output 2 working mode
Cur tEn
2AOF
nu
Pr2
Analog output 2 function
nu InC1 InC2 InF
2AOM
0
Pr2
Minimum value of analogue output 2
0 ÷ 100 (%)
2AOt
0
Pr2
Time with analog output 2 at max when after
exceeding AOM
0÷15s
2MPM
100
Pr2
Maximum % variation per minute, analog
output 2
nu, 1 ÷ 100%
2SAO
50
Pr2
Percentage of analog output 2 in case of
probe failure
0 ÷ 100 (%)
2AOH
70
Pr2
Maximum analog output 2 percentage when
silence mode function is enabled
0 ÷ 100 (%)
tbA
YES
Pr1
Alarm relay silencing
no - yES
OAP
cL
Pr2
Polarity alarm relay
OP - CL
oFF
no
Pr2
off function enabled
no - yES
bUr
YES
Pr2
Buzzer enabled
no - yES
Adr
1
Pr2
Serial address
1 ÷ 247
rEL
3.4
Pr2
Release firmware
Readable only
Ptb
Pr2
Parameter table code
Readable only
Pr2
-
Pr1
Pr2 access
Readable only

Related product manuals