Digital Monitoring Products XR500 Series Installation Guide
32
COMPLIANCE
30.7 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone number,
unless that phone number is specically provided for that purpose.
30.8 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by
the installing alarm company and frequent testing by the end user is essential. Oering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing
alarm company.
30.9 Audible Alarm
Fire Type zones must be programmed to activate an audible alarm. The Bell Action for Fire Type zones must not be
programmed as N (None).
30.10 Fire Zone Programming
If a retard delay is used on a waterow zone, it cannot exceed 90 seconds and any retard delay in the waterow
initiating devices must be subtracted from the 90 seconds al lowed. The retard delay should not be used on a zone
with smoke detectors.
30.11 Class A Style D Zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Class A Style D zones to the
Model XR500 Series. See the 869 Installation Guide (LT-0186) and this guide for wiring information.
30.12 Listed Receivers
Operation has been veried with the DMP SCS-VR and SCS-1R receivers and any Central Station Receiver that accepts
industry standard Contact ID (DTMF) format. It is the installer’s responsibility to verify compatibility between the
panel and the receiver used during installation. The installer shall verify the compatibility of the receiver and the
system on a yearly basis.
30.13 Standby Batteries
For UL listed applications, the panel must have 24 hour battery standby operation. The Model 364 battery should not
be used for re installations.