EasyManua.ls Logo

DOLD DMP 96 A - Line Compensation, Zero-Point Offset; Line Compensation; Zero-Point Offset

DOLD DMP 96 A
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006
24
Display: Parameter:
"SEn" Sensor ID as in table
Sensor ID:
Sensor
ID:
ID by ordering
key:
Sensor: Max. display
range:
Max. setpoint
range:
Display:
P 1 P 1 Pt 100 -69...149°C -50...100°C 3 digits
P 2 P 2 Pt 100 -69...249°C -50...200°C 3 digits
P 3 P 3 Pt 100 -69...349°C -50...300°C 3 digits
P 4 P 4 Pt 100 -69...699°C -50...600°C 3 digits
P 5 P 5 Pt 100 -169...149°C -150...100°C 4 digits
tL1 L 1 Fe-CuNi Type L -24...499°C 0...450°C 3 digi ts
tL2 L 2 Fe-CuNi Type L -24...899°C 0...850°C 3 digi ts
tn1 K 1 Ni Cr-Ni Type K -24...649°C 0...600°C 3 dig its
tn2 K 2 Ni Cr-Ni Type K -24...1299°C 0...1200°C 4 d igits
8. Line compensation, zero-point offset:
8.1 Line compensation:
Line compensation is required only with resistance thermometers in two-wire technology. Line
resistance can be counterbalanced with the "Cor" parameter (configuration level).
Proceed as follows to generate line compensation:
1. Connect a 100 resistor to the end of the sensor line (corresponds to 0°C).
2. Read off the actual value from the display.
3. Jump to the configuration level.
4. Correct line resistance (display in °C) with the "Cor" parameter.
Example: 1. Displayed actual value: +3.0°C
2. "Cor" value to be set on the configuration level: -3.0°C
3. Confirm the set value with the P key.
Return to operating mode
4. Display of actual value: 0.0°C
5. Remove 100 resistor from end of line.
8.2 Zero-point offset:
The "Cor" parameter can also be used for zero-point offset (offset value) towards plus or minus
(as in the above example).