DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006
7
Housing: Pull-out housing for mounting control panel per DIN 43 700
with a B fastener as per DIN 43 835 (M 4 screw clamp)
Material: PPO, glass-fiber reinforced (Noryl GFN2SE1)
self-extinguishing, non-dripping
fire protection class UL 94 V1
Front panel dimensions: 96 x 96 mm DIN 43 700
Control panel cutout: 92
+0.8
x 92
+0.8
mm
Recess depth: approx. 92 mm including screwed plug connector
Terminal connections: Screwed socket strips
nominal cross section 2.5 mm
2
Weight: approx. 500 g
Ambient conditions: Operating temperature range: 0...+50°C
Storage temperature range: -30...+70°C
Climatic utilization category: as per DIN 40 040,
corresponding to 75% relative humidity
without moisture condensation.
2. Technical data, inputs:
2.1 Analog inputs:
Input as per identification plate or sensor ID:
• Pt 100 three-wire lead
• Fe-CuNi thermal converter, Type L
• Ni Cr-Ni thermal converter, Type K.
Sensor ID:
Sensor: Sensor
ID:
ID according to
ordering key:
Max. display
range:
Max. setpoint
range:
Program
version:
Pt 100 P 1 P 1 -69...149°C -50...100°C 020H0
Pt 100 P 2 P 2 -69...249°C -50...200°C 020H1
Pt 100 P 3 P 3 -69...349°C -50...300°C 020H2
Pt 100 P 4 P 4 -69...699°C -50...600°C 020H3
Pt 100 P 5 P 5 -169...149°C -150...100°C 020H4
Fe-CuNi Type L
tL1 L 1 -24...499°C 0...450°C 020H5
Fe-CuNi Type L
tL2 L 2 -24...899°C 0...850°C 020H6
Ni Cr-Ni Type K
tn1 K 1 -24...649°C 0...600°C 020H7
Ni Cr-Ni Type K
tn2 K 2 -24...1299°C 0...1200°C 020H8
(See Information Level, Section 8.7, for instructions on querying sensor ID).
2.1.1 Technical Data, inputs:
Pt 100: Sensor current: constant 1 mA DC
Calibration precision: ≤ 0,15 % F.S.
Linearity error: ≤ 0,1% F.S.
Temperature drift characteristics: ≤ 100 ppm/K
Equipped with sensor breakage cutoff and short circuit fuse