The load circuits of the relays have to be protected against excessive currents in order to avoid
the relay contacts becoming welded together.
The device must not be installed in an ex-area.
If used for purposes other than originally intended the device may be damaged and cause dam-
age to connected installations.
The life time of the relays is limited to 10
6
switching cycles at a load of 500 VA. Thus it is to a
high degree dependent on the frequency of switching cycles.
Time per switching cycle Time after which 10
6
switching cycles are reached
(operation: 8 hours/day at a load of 500 VA)
120 s about 11.4 years
60 s about 5.7 years
30 s about 2.8 years
This table is invalid for Solid-State-Relay.
At low loads life time increases with regard to the values indicated in the table.
The device is to be protected against moisture (especially condensing moisture) and excessive
contamination. If this is not assured the device is liable to malfunctions.
Unplug connecting plugs only longitudinally to plug direction. Under no circumstances must the
connecting plugs be plugged in or out obliquely!
Furthermore care must be taken that the surrounding temperature corresponds to the values
shown in the specifications. Sufficient air circulation must be provided.
These operating instructions do not contain all directions to regulations, standards etc. which
become effective when using this device in connection with other installations. These regula-
tions, standards etc. must be ascertained and abided to by the purchaser.
1.2 Identification plate:
The following information is
important and should be given
Type of controller
Factory number
Program version
Model number
DMP 96 A
Operating voltage:
Switching capacity:
Factory number:
Input:
Logic input:
Outputs:
Model No:
ASP 675XXX
XXX V +/-10%
500 VA at 230 V AC
configurable function
Logic outputs
relay
Program version:
Type of controller
as per order
as per order
as per order
XXXXX
Terminal connection diagram number
whenever you have any technical
questions:
Figure 1: DMP 96 A identification plate