DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006
15
Display: Parameter: Range: Factory
setting:
"SP.2" Setpoint 2
(appears only for configuration "Co.L" = 01)
"rA.L...rA.H"
0.0°C
" y " Setpoint manipulated variable
(appears only for configuration "Aut" = OFF)
0.0...100% 0.0%
P
Display value is accepted
When configuring parameter ”Co.u” = on (setting setpoint via setpoint entry level) it is not possi-
ble to jump to the operator level.
7.3.2 Setting the setpoint level via the setpoint entry level:
P
Press for approx. 3 s to get display: " Cod "
100
Enter code: 77
P
Confirm code: Display: " uSr "
P
Jump to setpoint entry level.
Display: Parameter: Range: Factory
setting:
"SP.1" Setpoint 1 "rA.L...rA.H"
0.0°C
"SP.2" Setpoint 2
(appears only for configuration "Co.L" = 01)
"rA.L...rA.H"
0.0°C
" y " Setpoint manipulated variable
(appears only for configuration "Aut" = OFF)
0.0...100% 0.0%
P
Displayed value is accepted
When configuring parameter ”Co.u” = OFF (setting setpoint via operator level) it is not possible
to jump to the setpoint entry level.
7.4 The configuration level:
P
Press for approx. 3 s to get display: " Cod "
100