DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006
16
Enter code: 155
P
Confirm code: Display: " Con "
P
Jump to configuration level.
Display: Parameter: Range: Factory
setting:
"Cor" Line compensation and zero-point offset -25...25.0°C
0.0°C
"rA.H" Set upper limit of setpoint range
(end of setpoint range)
max. set-
point range
by sensor ID
(Section 2.1)
max. set-
point range
by sensor ID
(Section 2.1)
"rA.L" Set lower limit of setpoint range
(beginning of setpoint range)
Note: With configuration "rA.H" = "rA.L" it is
not possible to set the setpoint on the
operator level.
With configuration "rA.H" < "rA.L"
the keys
or can be used
to switch back and forth between the
set values
max. set-
point range
by sensor ID
(Section 2.1)
0.0°C
"Co.1" Configuration of control output or limit com-
parator K 1
Two-point controller / three-point response:
01: Cooling controller with hysteresis
setting towards plus
02: Cooling controller with PID feedback
03: Limit comparator closed in goodband
(hysteresis fix at 0.5 K)
04: Heating controller with adjustable
hysteresis towards minus
05: Heating controller with PID feedback
06: Limit comparator open in goodband
(hysteresis fix at 0.5 K)
Continuous-action controller:
(parameter "Co.A" = 03 or 04,
relay contact K 1 deactivated).
02: rising characteristic with PID "cool-
ing" feedback
05: falling characteristic with PID "heat-
ing" feedback
01...06 05