DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006
17
Display: Parameter: Range: Factory
setting:
"Co.2" Configuration of limit-value contact K 2
00: Relay deactivated (no function)
01: Absolute limit value of make contact
relative to rising temperature
02: Limit value travels with setpoint,
make contact relative to rising temp.
03: Limit comparator closed in goodband
(hysteresis fix at 0.5 K)
04: Absolute limit value, break contact
referenced to rising temperature
05: Limit value travels with setpoint,
break contact relative to rising temp.
06: Limit comparator open in goodband
(hysteresis fix at 0.5 K)
00...06 00
"Fd.1"
"Fd.2"
Error allocation, outputs K 1; K 2
Output K 1
Output K 2
on: Output active in the event of error
OFF: Output inactive in the event of error
on...OFF
OFF
OFF
"rES" Display resolution
00: resolution 0.1K
01: resolution 1K
00...01 00
"Aut" Automatic function
on: Automatic function mode activated
(controller)
OFF: Automatic function mode deactivated
(actuator).
The
key can be used to switch
from automatic function mode (con-
troller) to manual function mode (ac-
tuator).
on...OFF on
"Co.u" Setting of setpoint via setpoint entry level
on: Setting of setpoint via setpoint entry
level activated
OFF: Setting of setpoint via setpoint entry
level deactivated (setpoint set via
operator level).
on...OFF OFF
"Co.A" Analog output:
Analog output of actual value (optional):
00: Analog output deactivated
01: Voltage/current output: 0...1 V DC,
0...2 V DC, 0...5 V DC or 0...20 mA
02: Current output: 4...20 mA
Continuous-action controller:
(parameter "Co.A" = 03 or 04),
configure the desired control function (pa-
rameter "Co.1" = 02 or 05), (relay contact K 1
is deactivated):
03: Voltage/current output: 0...1 V DC,
0...2 V DC, 0...5 V DC or 0...20 mA
04: Current output: 4...20 mA
00...04 00