DOLD GMBH Operating instructions DMP 96 A
DMP 96 A Version: 020 Number of pages: 26
H0e020bA4.doc Edition: 07.11.2006
18
Display: Parameter: Range: Factory
setting:
"An.H" Analog output of actual value
High-end value of measuring range limit
max. display
range de-
pendent on
sensor ID
(Section 2.1)
end of set-
point range
dependent
on sensor ID
(Section 2.1)
"An.L" Analog output of actual value
Low-end value of measuring range limit
max. display
range de-
pendent on
sensor ID
(Section 2.1)
0.0°C
"Co.L" Configuration of logic input
00: Logic input deactivated
01: Changing setpoint selection
contact open: setpoint 1
contact closed: setpoint 2
02: Stop function
(not in effect with continuous-action
control output!)
Contact closed:
control contact K 1 deactivated and
setpoint display goes dark
(lower display)
03: Programming block
Contact closed:
programming function released
Contact open:
programming function blocked
(jump to configuration, para- me-
terization, setpoint entry and self- opti-
mization levels blocked).
00...03 00
"3-P" Three-point response
on: Three-point response activated
OFF: Three-point response deactivated
Configuring three-point response
e.g.: heating K 1: "Co.1" = 04 or 05,
cooling K 2: "Co.2" = 02
cooling K 1: "Co.1" = 01 or 02,
heating K 2: "Co.2" = 05
spreading (parameter ”Lr.2”) toward
plus or setting towards minus.
on...OFF OFF
Important:
After any change of configuration or reconfiguration of outputs K 1 and
K 2 (parameters "Co.1" and "Co.2") the corresponding parameters on
the parameterization must be set and adapted to the directly controlled
member.
After any change of configuration or reconfiguration of the setpoint ran-
ge (parameters "rA.H" and "rA.L") the setpoint settings on the operator
level, and the setpoint entry level must be checked and adapted to the
setpoint range.