EasyManuals Logo

Dometic PGD1 User Manual

Dometic PGD1
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10
EN
General Information VARC Chiller Controls
Parameter VARCX48 VARCX60 VARCX72 VARCX120 Data Type
Condenser Frost Protection
Cond Setpoint 30 30 30 30 Degrees F
Cond Band 2.5 2.5 2.5 2.5 Degrees F
Comp Speed 60 40 40 40 RPS
Compressor PID
Cntrl P P P P
K 50 50 50 50
Chilled Water High Temperature Limit Alarm
Setpoint 125 125 125 125 Degrees F
Off Band (SP-) 15 15 15 15 Degrees F
Retries 6 6 6 6
Retry Timeout 30 30 30 30 Minutes
Retry Delay 120 120 120 120 Seconds
Chilled Water Freeze Limit Alarm
Setpoint 36 36 36 36 Degrees F
Off Band (SP+) 5.4 5.4 5.4 5.4 Degrees F
Retries 6 6 6 6
Retry Timeout 10 10 10 10 Minutes
Retry Delay 120 120 120 120 Seconds
Chilled Water Flow Alarm
Retries 6 6 6 6
Retry Timeout 10 10 10 10 Minutes
Retry Delay 120 120 120 120 Seconds
High Discharge Pressure Alarm
Retries 6 6 6 6
Retry Timeout 30 30 30 30 Minutes
Retry Delay 120 120 120 120 Seconds
High Pressure Switch Alarm
Retry 6 6 6 6
Retry Timeout 30 30 30 30 Minutes
Retry Delay 120 120 120 120 Seconds
Low Suction Alarm
Low Suction Pressure 60 60 60 60 PSI
Delay 180 180 180 180 Seconds
Retries 6 6 6 6
Retry Timeout 30 30 30 30 Minutes
Retry Delay 120 120 120 120 Seconds

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dometic PGD1 and is the answer not in the manual?

Dometic PGD1 Specifications

General IconGeneral
BrandDometic
ModelPGD1
CategoryControl Unit
LanguageEnglish

Related product manuals