Traucjumu novršana | lv
Lietošanas instrukcija | Dräger Polytron
®
6100 EC WL, Dräger Polytron
®
Repeater ISA 141
11.1 ISA100 Wireless
™
standarta objekti
11.2 Mērījuma vērtības statuss (PV_STATUS)
Nozme "Quality" (Bits 6 un 7):
0: Slikti(Bad) – mrjuma vrtba netiek prraidta.
1: Nenoteikts (Uncertain) – mrjuma vrtbas kvalitte ir mazka par normlu.
2: Labi (Good) – mrjuma vrtbas kvalitte ir laba, bet ir iespjami trauksmes apstki.
Rādījums Piekļuve Okteta Nr. Saturs Modbus-Input register Datu tips
PV READ 1 PV_Status Register N UINT (16 biti)
PV READ 2 PV_Value (1/4)
Register N+1
32 bitu plsma (4 okteti),
Float32 pc IEEE 754
PV READ 3 PV_Value (2/4)
PV READ 4 PV_Value (3/4)
Register N+2
PV READ 5 PV_Value (4/4)
DIAG_STATUS READ 1 Diag_Status (1/4)
Register M UINT (16 biti)
DIAG_STATUS READ 2 Diag_Status (2/4)
DIAG_STATUS READ 3 Diag_Status (3/4)
Register M+1 UINT (16 biti)
DIAG_STATUS READ 4 Diag_Status (4/4)
Quality Substatus
Bits 6 un 7 Bits no 2 līdz 4 PV Cēlonis Novēršana
0 0 NaN Palaides secba ir aktva. Nogaidiet palaides secbu.
Palaides secba neizdevs, nav atpazta EC mr-
jumu galva.
AStartjiet gzes mrierci no jauna.
BLdziet DrägerService prbaudt gzes mrie-
rci.
0 1 NaN Aktivizta sensora blošanas funkcija. Izmantots
sensors ar atširgu daas numuru.
Izmantojiet sensoru ar to pašu daas numuru vai
deaktivizjiet sensora blošanas funkciju.