344 Instrucţiuni de utilizare | Dräger Polytron
®
6100 EC WL, Dräger Polytron
®
Repeater ISA
ro | Remedierea avariilor
11.1 Obiecte standard ISA100 Wireless
11.2 Statusul valorii măsurate (PV_STATUS)
Semnificaie "Quality" (Bit 6 i 7):
0: Necorespunztor (Bad) – Nici o transmitere de valoare de msurare.
1: Incert (Uncertain) – Calitatea msurrii mai slab decât normal.
2: Bun (Good) – Calitatea msurrii este bun dar pot s fie prezente condiii de alarm.
Afişaj Acces Octet Nr. Cuprins Registru intrare Mod-
bus
Tip date
PV READ 1 PV_Status Register N UINT (16 Bit)
PV READ 2 PV_Value (1/4)
Register N+1
32-Bit-Float (4 Octei),
Float32 conform
IEEE 754
PV READ 3 PV_Value (2/4)
PV READ 4 PV_Value (3/4)
Register N+2
PV READ 5 PV_Value (4/4)
DIAG_STATUS READ 1 Diag_Status (1/4)
Register M UINT (16 Bit)
DIAG_STATUS READ 2 Diag_Status (2/4)
DIAG_STATUS READ 3 Diag_Status (3/4)
Register M+1 UINT (16 Bit)
DIAG_STATUS READ 4 Diag_Status (4/4)
Quality Substatus
Bit 6 şi 7 Bit 2 până la 4 PV Cauză Remediere
00NaNSecvena de start activ.Ateptai secvena de start.
Secvena de start euat, nici un cap de msurare
identificat.
A Repornii aparatul de msurare gaz.
B Solicitai verificarea aparatului de msurare
gaz de ctre DrägerService.
01NaNFuncia de blocare a senzorului este activat. A
fost montat un senzor cu numr de pies diferit.
Folosii un senzor cu acelai numr de pies sau
dezactivai funcia de blocare a senzorului.