EasyManua.ls Logo

Dru KAMARA 7KW - Flue Gas Discharge;Combustion Air Supply System; Placing the Appliance

Default Icon
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.5.2 Installation of wall-terminal and manifold
Follow the procedure below when installing the wall-
terminal and manifold:
Drill a hole in the wall, with a diameter of 105 mm.
Drill 3 holes in the wall from the outside, for mounting
the wall-terminal.
!Caution - Place the wall terminal with the groove/
folded seam at the top;
Glue the sealing/gasket of the wall-terminal to the flange.
Temporarily mount the wall-terminal from the outside.
Slide the manifold from the inside as far as possible onto
the concentric tubes of the wall-terminal.
Determine the distance between manifold and wall.
Unscrew the wall-terminal.
Cut the wall-terminal to size.
Mount the wall-terminal for the final time.
Determine in which angle the manifold should be placed.
Apply a sufficient amount of heat-resistant sealant to the
outside of the galvanized steel combustion air supply tube.
Apply a film of heat resistant sealant to the inside of the
aluminium flue gas discharge tube.
Place the sealing/gasket of the manifold between wall and
manifold.
!Tip For the manifold, you can choose between two
combustion air supply connections.
Mount the manifold in the correct position.
Drill 3 holes in the wall for mounting the manifold.
Mount the manifold with the screws and washers supplied.
If necessary, apply a wall-terminal guard.
Place the wall-terminal guard centrally over the wall-
terminal.
5.6 Placing the appliance
Place the appliance as follows:
Caution - Do not make any changes to the
appliance;
- Do not cover the appliance and the
discharge material and/or do not wrap
it in an insulation blanket or any other
material;
- Mount the appliance to the wall using
the wall brackets; this will guarantee the
minimum required distance of 10 mm
from the back wall;
- Make sure there is a free outflow of
warm convection air at the front of the
appliance;
- Make sure there is a free supply of
cold convection air at both sides of the
appliance. Curtains, for example, could
block the inlet as a result of the sucking
action of the convection fan.
- Avoid that warm convection air can
recirculate through the cold convection
air inlet.
!Tip - Prevent construction grid/drill material from
contaminating the appliance;
- Only mount the casing, after performing the final
check in section 7.
Provide a gas connection at the location. For details, see
section 5.3.
Provide an electrical connection at the location. For
details, see section 5.4.
Remove the casing:
- Unscrew the screws at both sides of the casing
(see fig. 4);
- Lift the casing appr. 1 cm and slide/lift the casing to the
front.
Caution Avoid damaging the wiring when taking off
the mantel.
Place the appliance on its destined location.
Drill holes for mounting the appliance.
Attach the appliance to the wall, using the supplied plugs,
washers and screws.
5.7 Flue gas discharge / combustion air supply
system
5.7.1 Construction
For the 7kW and 12kW Power Flue, the maximum length
of the discharge tubes (vertical and horizontal) is 10
meters when using a maximum of 2 bends of 90º; when
3 bends of 90º will be used, the total maximum length of
the discharge system is 6 meters, and when 4 bends of 90º
will be used, the maximum length is 2 meters.
For the 16 kW Power Flue, the maximum length of the
discharge tubes (vertical and horizontal) is 3 meters, with
a maximum of 1 bend of 90°.
Depending on the construction, the appliance is set by
means of a restriction.
INSTRUCTIONS FOR INSTALLATION
8
!
!
Fig. 4

Table of Contents

Related product manuals