Table
5-1
Troubleshooting
reference
Troubleshooting
Reference
Problem
Overload
shutdown
Run time
is
less than
expected.
Possible
Cause
Appliance power
requirements exceed the
capability
of
the
Duracell® Powerpack.
Duracell® Powerpack
battery
is
not fully
charged.
AC appliance power
consumption is higher
than expected.
Environmental
temperature is less than
O°C
(32°F) or more than
40°C (104°F)
Solution
Unplug the appliance and
confirm that the appliance's
power requirement is 300 W or
less before attempting to restart
the appliance.
Recharge using the AC charger,
until Battery Status LED is
green.
Check AC appliance power or
wattage rating (or current draw
for
12
V DC appliances) and
compare with Table
3-1
on
page
15
and Table 3-2 on
page 18.
Operate within correct
temperature range.