3 Installation and Configuration
Environmental Requirements
Cleanliness
The battery system has high voltage connectors. The environmental conditions will affect
the isolation of the system.
Before installation and switch-on, dust and swarf must be removed to keep the system
clean. The environment must be dust-proof to a certain extent.
Dust and humidity must be regularly checked during continuous operation of the system.
Fire Protection System
The room must be equipped with a fire protection system or fire extinguishers
(Recommended: foam extinguisher). The fire protection system needs to be regularly
checked to ensure its normal condition. Please refer to your local fire protection
equipment for use and maintenance requirements.
Grounding System
Make sure that the grounding point for the battery system is stable and reliable before
installation. If the battery system is installed in an independent equipment cabin (e.g.
container), make sure that the grounding of the cabin is stable and reliable.
The resistance of the grounding system must be ≤100mΩ.
Temperature
Tower system operating temperature range: 0°C to +50°C; Optimal temperature: 18°C to
30°C; Exceeding the working temperature range will cause
over-temperature/under-temperature alarms or protection of the battery system which
may lead to shortening the life cycle.
Cooling System
It is essential to equip a cooling system to keep the battery system in a relevant
temperature range. Over-temperature/ under-temperature alarms or protection of the
battery system may lead to shortening the life cycle.
Heating System
It is essential to equip a heating system to keep the battery system in a relevant
temperature range. If the temperature is below 0°C, the system may shut down for
protection. It is necessary to open the heating system first. Exceeding or falling below the
operating temperature range will cause over-temperature/under-temperature alarms or
protection of the battery system may lead to shortening the life cycle.