SPECIFICATIONS
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide S 164201642 Rev C www.eaton.com/powerquality
96
Table 13. Environmental and Safety Specifications
Operating Temperature 50°F to 104°F (10°C to 40°C) Optimal battery performance: 77°F (25°C)
Transit Temperature -13°F to 131°F (-25°C to 55°C)
Storage Temperature 32°F to 77°F (0°C to 25°C)
Recommended battery storage: 59°F to 77°F (15°C to 25°C)
Ventilation Front air intake, forced air, two fans, positive pressurization, temperature
UPS-monitored
Altitude 9,843 ft (3,000m) operating without derating
32,810 ft (10,000m) during transportation
Relative Humidity 5–95% noncondensing
Audible Noise <56 dBA at 1 meter distance, typical loads
<62 dBA for heavy load, high ambient or high altitude, on battery
Surge Suppression ANSI C62.41 Category B3
Safety Conformance NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;
Agency Markings cULus
EMC (Class A) IEC 62040-2, FCC Part 15, ICES-003