SPECIFICATIONS
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide S 164201642 Rev C www.eaton.com/powerquality
98
Table 15. Model Specifications
10 kVA Model 15 kVA Model
Output Voltage (Line–Line) 208
Output Voltage (Line–Neutral) 120
Input Voltage 208
Input Current 32A 48A
Output Current 27.8A 41.6A
Output kVA 10 15
Output kW 9 13.5
Efficiency (Minimum) 89% 90%
Heat Rejection [BTU/hr (kg-cal/hr)] 3798 (956) 5122 (1290)
Main Disconnect Breaker 65k AIC
(ampere interrupting capacity)
Short Circuit Rating 10 kA
Table 16. Battery Specifications
Battery Type 17 Ah sealed, valve-regulated lead acid (VRLA), maintenance-free, minimum 3-year float
service life at 25°C (77°F), voltage 192 Vdc (96 cells per string)
Number of Strings 1 string
Battery Replacement Must be replaced by a qualified service technician
Charger Service configurable 0.5–34A per string, with overall maximum of 34A (limited by input
current). Default: 3.4A per string
Charging Approximately 3 hours to 80% usable capacity at nominal line voltage after full load
discharge
Start-on-Battery Allows start of UPS without utility input
Performance ABM technology increases battery service life, optimizes recharge time, and provides a
warning before the end of useful battery life