UPS INSTALLATION
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide S 164201642 Rev C www.eaton.com/powerquality
27
Figure 10. UPS Terminal Block
13. Optional. Hard wire the remote EMO terminations for the UPS
according to the following table.
Remote EMO Connections
Wire Function Terminal Wire Size Rating Suggested Wire Size
Remote
EMO
TB5-1
12–22 AWG
(4–0.32 mm
2
)
18 AWG (0.82 mm
2
)
TB5-2