68 Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
NOTE When installing UVR and battery aux interface wiring to the UPS interface terminals,
conduit must be installed between the UPS and battery system.
5. Remove the UPS cabinet interface entry conduit landing plates to drill or punch holes (see Figure 28).
6. Reinstall the interface entry plates and install the conduit.
NOTE The 9395XC system can trip a maximum of six battery cabinets total. This applies to
both the 1085 standard and High Rate series batteries. If more than six battery cabinets
in total are needed in a separate UPM battery configuration, DO NOT hook up the UVRs.
7. Route the UVR and battery aux wiring from the battery disconnects to the UPS cabinet. See Figure 28 for
UPS wiring access information and terminal locations.
8. Connect the wiring to TB1 terminals.
9. Reinstall the deadfront panel.
10. If wiring Minislot connections, proceed to paragraph 4.7.3 Minislot Connections; otherwise, proceed to
Step 12.
11. Close the door and secure the latch.
Figure 36. Typical Battery Interface Connection
Battery
Disconnect
TB1
Battery Aux
Battery Aux Common
48 Vdc UVR +
48 Vdc Battery UVR –
UPS
UVR
5
6
7
8
NOTE: Battery aux and DC UVR wiring should be a minimum of 18 AWG.
48 Vdc
44..77..33 MMiinniisslloott CCoonnnneeccttiioonnss
NOTE LAN and telephone drops for use with Minislot cards must be provided by the customer.
NOTE When installing external wiring to Minislot cards, a conduit must be installed to the UPS
cabinet. When installing internal wiring to Minislot terminals, route the wiring through
the internal opening in the Minislot communication bay and the interface entry conduit
landing plates.
For installation and setup of an Minislot card, contact an Eaton service representative (see 1.8 Getting Help).
To install wiring to connections:
UPS System Installation