Figure 11. 93PM G2 UPS top dimensions, with top-air exhaust option
The UPS cabinets use forced air cooling to regulate internal component temperature. By standard, air
inlets are in the front of the cabinet and outlets are in the back. You must allow clearance in front of and
behind each cabinet for proper air circulation.
With the optional top air exhaust kit, it is possible to configure the air outlets in the top rear of the cabinet.
With this option, the UPS can be installed against a wall or back-to-back.
The clearances required around the UPS cabinet in both of these situations are shown in Table
6: UPS
cabinet clearances.
Table 6. UPS cabinet clearances
Eaton 93PM G2 xxx(200) and 93PM
G2 xxx(300) models
Eaton 93PM G2 xxx(240) and 93PM
G2 xxx(360) models
From the top of the cabinet 400 mm 500 mm
From the front of the cabinet 1000 mm 1000 mm
From the back of the cabinet 200 mm* 300 mm*
From the side of the cabinet 0 mm 0 mm
*) 0 mm if top air exhaust kit installed
Figure 12. 93PM G2 UPS cabinet clearances
Z = clearance at the
back
Y = clearance at the top X = clearance at the front
EATON 93PM G2 UPS USER’S AND INSTALLATION GUIDE P-164000956
-