UPS CTO models Battery cable, pos. & neg.
line [mm
2
] Battery PE cable Battery fuse [A]
93PM G2 xxx(180) 0.9
pF
2 x 95 per pole
95 630
93PM G2 xxx(250) 2 x 120 per pole
120 700
93PM G2 xxx(300) 0.9
pF
2 x 150 per pole
150 800
NOTE: UPS power upgrading is possible only if the sizing of the external cables is sufficient. Alternatively,
the external cabling must be upgraded as well. Fuses are of the type gG.
Cable sizing is based on the standard IEC 60364-5-52 table B.52.2 and IEC 60364-5-54 table B.54.2.
Sizing is for 70 ºC rated copper cables.
Table 11. Rated and maximum currents for each 200kW/240kVA model configuration for rated power and
voltage, rectifier input and UPS output / bypass
UPS standard models
Rated voltage [V]
Rectifier input
UPS output / bypass
Rated current [A]Rated current [A] Maximum current [A]
93PM G2 xxx(200) 380 361 384 304
400 343 384 289
415 331 384 278
93PM G2 xxx(240) 0.9
pF
380 374 384 365
400 371 384 346
415 358 384 334
UPS CTO models
Rated voltage [V]
Rectifier input
UPS output / bypass
Rated current [A]Rated current [A] Maximum current [A]
93PM G2 xxx(100) 380 181 192 152
400 172 192 144
415 166 192 139
93PM G2 xxx(120) 0.9
pF
380 187 192 182
400 186 192 173
415 179 192 167
93PM G2 xxx(150) 0.9
pF
380 260 288 228
400 258 288 217
415 248 288 209
93PM G2 xxx(180) 0.9
pF
380 281 288 273
EATON 93PM G2 UPS USER’S AND INSTALLATION GUIDE P-164000956
-