400 278 288 260
415 268 288 250
Table 12. Rated and maximum currents for each 300kW/360kVA model configuration for rated power and
voltage, rectifier input and UPS output / bypass
UPS standard models
Rated voltage [V]
Rectifier input
UPS output / bypass
Rated current [A]Rated current [A] Maximum current [A]
93PM G2 xxx(300) 380 542 576 456
400 515 576 433
415 496 576 417
93PM G2 xxx(360) 0.9
pF
380 561 576 547
400 557 576 520
415 537 576 501
UPS CTO models
Rated voltage [V]
Rectifier input
UPS output / bypass
Rated current [A]Rated current [A] Maximum current [A]
93PM G2 xxx(100) 380 181 192 152
400 172 192 144
415 166 192 139
93PM G2 xxx(120) 0.9
pF
380 187 192 182
400 186 192 173
415 179 192 167
93PM G2 xxx(150) 0.9
pF
380 271 288 228
400 258 288 217
415 248 288 209
93PM G2 xxx(180) 0.9
pF
380 281 288 273
400 278 288 260
415 268 288 250
93PM G2 xxx(200) 380 361 384 304
400 343 384 289
415 331 384 278
93PM G2 xxx(240) 0.9
pF
380 374 384 365
400 371 384 346
EATON 93PM G2 UPS USER’S AND INSTALLATION GUIDE P-164000956
-
February 2021 www.eaton.eu 4400