415 358 384 334
93PM G2 xxx(250) 380 452 480 380
400 429 480 361
415 414 480 348
93PM G2 xxx(300) 0.9
pF
380 468 480 456
400 464 480 433
415 447 480 417
NOTE: Maximum rectifier current calculated at the -15% voltage tolerance and 102% continuous overload.
Table 13. Rated and maximum currents for rated power and voltage, battery
UPS standard models Battery
Rated current [A] Maximum current* [A]
93PM G2 xxx(200)
455 554
93PM G2 xxx(240) 0.9 pF
491 599
93PM G2 xxx(200)
682 832
93PM G2 xxx(360) 0.9 pF
736 898
*) Maximum battery current calculated at rated load in the end of discharge of VRLA battery (1.67 V per
cell).
UPS CTO models Battery
Rated current [A] Maximum current* [A]
93PM G2 xxx(100)
227 277
93PM G2 xxx(120) 0.9 pF
273 299
93PM G2 xxx(150)
341 416
93PM G2 xxx(180) 0.9 pF
409 449
93PM G2 xxx(200)
455 554
93PM G2 xxx(240) 0.9 pF
545 599
93PM G2 xxx(250)
568 693
93PM G2 xxx(300) 0.9 pF
682 749
*) Maximum battery current calculated at rated load in the end of discharge of VRLA battery (1.67 V per
cell).
EATON 93PM G2 UPS USER’S AND INSTALLATION GUIDE P-164000956
-
February 2021 www.eaton.eu 4411