EasyManua.ls Logo

Eaton 9PX 2200 GRT - Page 16

Eaton 9PX 2200 GRT
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 16
9PX 1-3 KVA US_EN
2. Presentation
Submenu Available settings Default settings
Com settings
Output signals [Relay] [DB9-1] [DB9-7] [DB9-8]
Sets events or fault that will actuate
Output signal parameters through
external contact connector or RS232
port
[Relay]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-1]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-7]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-8]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[Relay] [Bypass]
[DB9-1] [Low bat]
[DB9-7] [UPS OK]
[DB9-8] [On bat]
Remote command [Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
[Enabled]
Shutdown
commands
[Send CMD] [Output OFF] [OFF delay]
[restart]
Sets events or fault that will actuate
Output signal parameters through
external contact connector or RS232
port
[Send CMD]: [Yes] [No]
[Output OFF]: [No] [UPS] [Group 1]
[Group 2] [Group 1 + Group 2]
[OFF delay]: [0s] …[999s]
[Restart]: [Yes] [No]
Send CMD: [No]
Output OFF: [No]
OFF delay: [0s]
Restart: [Yes]
On battery notice
delay
[0s] ... [99s]
Sets delay before noticing on battery
information to software.
[0s]
General alarm [On battery] [Battery fault]
[Overload pre-alarm] [Internal fault]
[Ambient temp.] [Fan lock]
[Bypass overload] [Current limit]
[Short circuit] [Inverter overload]
[Power overload] [Low battery]
[On bypass] [UPS OK] [Load protected]
[Load powered] [Ext. charger ON]
Defines which event or fault generate
a general alarm through Output signal
screen.
[Internal fault]