Eaton 9PX 6000 G - Power Cables Connection; Access to Terminal Blocks; Input;Output Connection

Eaton 9PX 6000 G
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 24
5-6kVA US_EN
4. Power cables connection
4.1 Access to terminal blocks
1. Remove the terminal blocks cover (one screw)
2. Punch the knockouts and insert the cables/conduits inside
Note: the L6-30P input power cable is attached by Eaton.
9PX 6000 G only
• High leakage current:
Earth connection essential before connecting supply.
4.2 Input/Output connection
This type of connection must be carried out by qualified electrical personnel
Before carrying out any connection, check that the upstream protection device (Normal AC
source) is open "O" (Off). Always connect the ground wire first
If you ordered a HotSwap MBP or a PPDM, refer to the specific user manual to check the
terminal blocks connection of the UPS with this accessory.
OUTPUT NORMAL AC SOURCE
tt
L1L1
N(L2) N(L2)
1. Insert the Normal AC cable through the cable
gland.
2. Connect the three cables to the Normal AC source
terminal blocks.
3. Insert the Output cable through the cable gland.
4. Connect the three cables to the Output terminal
blocks.
5. Put back and secure the terminal blocks cover
with the screw.
6. Tighten the cable glands.