Page 27
5-6kVA US_EN
ENGLISH
5. Operation
5.4 Setting High Efciency mode
InHighEfciencymode,theUPSoperatesnormallyonBypassandtransferstoOnline(orBattery)mode
inlessthan10mswhenutilityfails.TransferstoHighEfciencymodewillbeactiveafter5minutes
of Bypass voltage monitoring: if Bypass quality is not in tolerance, then the UPS will remain in Online
mode.
Eaton recommends to use the HE mode only to protect I/T equipment.
TosettheHighEfciencymode:
1. Put the UPS on Bypass: press any button to activate the menu options, select Control and Go to
Bypass.
2. ThenpressEscapeandselectSettings,In/Outsettings,andHighEfciencymode.
3. SelectEnabledandEntertoconrm.
4. TheUPStransferstoHighEfciencymodein5minutes.
5.5 Conguring Bypass settings
ThefollowingsettingsareavailableforconguringBypassoperation.
Bypass transfer out of tolerance
1. Press any button to activate the menu options, then select Settings, Output settings, and Bypass
transfer.
2. SelectEnabledorDisabledforBPACNOK,andEntertoconrm.
If Enabled, the UPS transfers to Bypass even if Bypass AC source is out of tolerance, depending on
output mode. If Disabled, the UPS output is shutdown.
Interrupt time
This setting is displayed to define the break duration during transfer to Bypass, only if transfer out of
tolerance is enabled. 10 ms or 20 ms can be selected.
5.6 Conguring battery settings
Automatic battery test
Automatic battery tests are done every week in constant charging mode and at each cycle in ABM
mode. The tests frequency can be modified.
During the test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds under
load.
Battery mode is not displayed and battery low alarm does not activate during a battery test.
The battery test may be cancelled due to bad conditions, or failed.
Low battery warning
During discharge, the low battery alarm is activated if the battery capacity goes below 20%.
This threshold can be modified.
External battery setting
The number of Extended Battery Module is automatically detected, or can be set manually in number
of EBM or in Ah.
Deep discharge protection
This setting is recommended to avoid damaging the battery. Warranty is void if deep discharge protec-
tion is disabled.