10 Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
Table 6. User Settings (Continued)
Submenu Available Settings Default settings
Output mode Mode: [Industrial] [IT]
[Custom] Overload: [Inv>Stop]
[Inv>BP] [Inv>BP>Inv]
[IT] [Inv>BP>Inv] [Inv>Stop]
Short-circuit: [Inv>Stop]
[Inv>BP]
[Inv>BP>Inv]
Input volt hysteresis
Sets input voltage hysteresis
from [1] to |10V]
[10V]
High Efficiency mode
[Enabled] [Disabled] Power the
output from Bypass for high
efficiency
[Disabled]
Bypass settings
[Volt low] [80V] LV; [160V] HV;
[Volt high] [144V] LV; [276V] HV;
[Qualify] [In spec];
[Hz synch] [5%];
[Unsynch] [Half cycle]
Load segments
[Auto start delay] UPS: [0s]; Group1: [3s];
Group2: [6s] UPS: [Disabled];
[Auto shutdown delay] Group1: [Disabled]; Group2:
[Disabled]
Overload prealarm [10%] [102%] Load %
when overload alarm occurs
[102%]
On/Off Settings
Start/Restart
[Cold start] [Auto restart]
[Auto start] [Start on bypass]
[Cold start] [Auto restart] are
Enabled
[Auto start] [Start on bypass]
are Disabled
Forced reboot
[Enabled] [Disabled] [Enabled]
[Timer] [10s] [180s] [10s]
When mains recover during a
shutdown sequence: If set to
Enabled, shutdown sequence
will complete and wait 10
seconds prior to restart, If set
to Disabled, shutdown
sequence will not complete,
UPS stays on.
Energy saving
[Enabled] [Disabled] [Disabled]
[Timer] [1min] [15min] [5min]
[Level] [100W] [1000W] [100W]
User Settings