Start
Room temperature
is high?
Decrease
room temperature
Y UPS AVR too hot fault? End
UPS surrounding temperature
is high?
N
Y
Remove heat sourceY UPS AVR too hot fault? End
Confirm outtake airflow on rear
panel is block?
N
Clear dust or object
Y
Y UPS AVR too hot fault? EndN
Check Fan is rolling normally?
Clear dust or object
UPS AVR too hot fault? EndN
Y
End
Client Environment
UPS
Check CNTL
CNTL
Replace CNTL PCBAN UPS AVR too hot fault?
EndN
Check PSDR
PSDR
Y
Replace damaged
components
UPS AVR too hot fault?N
Replace PSDR
Y
Y
EndN
Y
N
Y
Shut down UPS and
Wait 10min or more for
cooling AVR TX
Shut down UPS and
Wait 10min or more for
cooling AVR TX
N
Shut down UPS and
Wait 10min or more for
cooling AVR TX
Shut down UPS and
Wait 10min or more for
cooling AVR TX
Check AVR TX OK? Replace AVR TX UPS AVR too hot fault? EndNN
AVR TX
Y
Y
UPS AVR too hot fault?
N
Replace ups
Y
UPS