EasyManua.ls Logo

Eaton CEAG ZB-S Series - Page 35

Eaton CEAG ZB-S Series
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
4.4.5 Circuit change-over modules overview (SKUs)
SKU CG-S 4x1,5A
Input
Nominal voltage AC
220-240 V
Nominal voltage DC
184-275 V
Rated frequency 50/60 Hz
Outputs
Nominal current
1,5 A
Short circuit current
1500 A
Switching cycles 10000
cos phi capacaitive 0,5 - 1,0
Environmental conditions
Ambient temperature +55° C
Protection class IP20
Degree of pollution 2
Distance ventilation slots 75 mm
Number of circuits 4
Rated current per circuit
1�5 A
Fuse protections per circuit 2�5 A
max� inrush peak current 60 A
max� cable diameter 2�5 mm
2
with STAR-Technology
Dimensions and weights approx� 0�83 kg
H x W X D (in mm) 170 x 55 x 155
Module width
1 TE (1 and 55 mm)
Item no� 400 71 347 840
SKU CG-S 2x3A
Input
Nominal voltage AC
220-240 V
Nominal voltage DC
184-275 V
Rated frequency 50/60 Hz
Outputs
Nominal current
3 A
Short circuit current
1500 A
Switching cycles 10000
cos phi capacaitive 0,5 - 1,0
Environmental conditions
Ambient temperature +55° C
Protection class IP20
Degree of pollution 2
Distance ventilation slots 75 mm
Number of circuits 2
Rated current per circuit 3 A
Fuse protections per circuit 5 A
max� inrush peak current 250 A
max� cable diameter 2�5 mm
2
with STAR-Technology
Dimensions and weights approx� 0�66 kg
H x W X D (in mm) 170 x 55 x 155
Module width
1 TE (1 and 55 mm)
Item no� 400 71 347 051
SKU CG-S 1x6A
Input
Nominal voltage AC
220-240 V
Nominal voltage DC
184-275 V
Rated frequency 50/60 Hz
Outputs
Nominal current
6 A
Short circuit current
1500 A
Switching cycles 10000
cos phi capacaitive 0,5 - 1,0
Environmental conditions
Ambient temperature +55° C
Protection class IP20
Degree of pollution 2
Distance ventilation slots 75 mm
Number of circuits 1
Rated current per circuit 6 A
Fuse protections per circuit 10 A
max� inrush peak current 250 A
max� cable diameter 2�5 mm
2
with STAR-Technology
Dimensions and weights approx� 0�49 kg
H x W X D (in mm) 170 x 55 x 155
Module width
1 TE (1 and 55 mm)
Item no� 400 71 347 345
SKU CG 2x3A
Input
Nominal voltage AC
220-240 V
Nominal voltage DC
184-275 V
Rated frequency 50/60 Hz
Outputs
Nominal current
3 A
Short circuit current
1500 A
Switching cycles 10000
cos phi capacaitive 0,5 - 1,0
Environmental conditions
Ambient temperature +55° C
Protection class IP20
Degree of pollution 2
Distance ventilation slots 75 mm
Number of circuits 2
Rated current per circuit 3 A
Fuse protections per circuit 5 A
max� inrush peak current 120 A
max� cable diameter 2�5 mm
2
without switching function for CG-S-EVGs
Dimensions and weights approx� 0�61 kg
H x W X D (in mm) 170 x 55 x 155
Module width
1 TE (1 and 55 mm)
Item no� 400 71 347 290

Table of Contents

Related product manuals