Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
9.1.4 BCM failure codes
Failure code request (Z571.0)
Please push the Service-Pin for a few seconds. The
failures running throw by flashing from the LED
“Loadfailure. Example: 3 x flash, short break, 5x flash

Error code 3 and 5. The request-mode ends automatically
when all error codes are shown.
Overview of the failure codes (Z571.0)
Code Source Failure description
Old failures
2 BCM Insulation fault Minus
3 BCM Insulation fault Plus
4 BCM Battery voltage under Minimum
5 BCM Battery voltage over Maximum
6 BCM Cable- / Battery break
7 BCM Booster disturbance
8 BCM Load disturbance
New failures
1
12 CM Temperature rise
13 CM Ventilator disturbance
14 CM General disturbance
15 BCM Voltage value at conservation charging
16 BCM CCB communication failure (No answer at a CM-request)
1
New failures are always in combination with the failure „Load distur-
bance.