46
4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
4.4.6.1 Determination of current consumption value from the battery
International description T5
Socket G5
Lamp power (W) 8W-VVG
Luminous flux ratio (%) 100 51 35
Switch setting 0 4 9
Number of luminaires /
Current consumption from the battery /
Apparent power
[A] [VA] [A] [VA] [A] [VA]
1
0�175 / 36 0�123 / 19 0�118 / 12
2 0�258 / 72 0�150 / 37 0�090 / 24
3 – 0�213 / 56 0�120 / 36
4 – 0�246 / 74 0�157 / 48
5 – 0�276 / 92 0�192 / 60
6 – 0�322 / 110 0�220 / 71
7 – – 0�240 / 83
8 – – 0�260 / 94
9 – – 0�280 / 105
Table 1. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%) at
20 °C ambient temperature at the luminaire.
International description T26
Socket G13
Lamp power (W) 58 36 18
Luminous flux ratio (%) 100 48 32 100 75 54 32 100 87 54 36
Switch setting 0 5 9 0 2 4 8 0 1 5 9
Number of luminaires /
Current consumption from the
battery / Apparent power
[A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [ [A] [VA] [A] [VA] [A] [VA] [A] [VA]
1
0�62 147 0�37 84 0�35 81 0�47 107 0�34 80 0�31 71 0�30 70 0�37 85 0�31 72 0�26 60 0�26 60
2 – – – – – – – –
0�59 137 0�47 109 0�36 83 – – 0�56 121 0�33 75 0�29 67
3 – – – – – – – – – – – – – – – – – –
0�47 108 0�35 82
Table 2. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%) at
20 °C ambient temperature at the luminaire.