EasyManua.ls Logo

Eaton CEAG ZB-S Series - Page 47

Eaton CEAG ZB-S Series
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
4 Construction and Function
Mounting and Operating Instructions CEAG Central Battery System ZB-S 40071860179 (L) November 2018 www.ceag.de
International description TC-L
Socket 2G11
Lamp power (W) 36 24 18
Luminous flux ratio (%) 100 59 43 100 73 57 46 100 71 52 47
Switch setting 0 5 9 0 3 6 9 0 3 7 9
Number of luminaires /
Current consumption from the
battery /
Apparent power
[A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA]
1
0�47 108 0�30 70 0�29 68 0�38 89 0�28 64 0�27 62 0�27 65 0�39 90 0�26 60 0�26 60 0�25 60
2
0�43 96 0�33 76 0�42 99 0�34 79 0�32 74 0�42 98 0�31 70 0�28 65
3
0�58 135 0�44 103 0�61 136 0�44 103 0�37 86 0�57 135 0�40 94 0�34 80
4
0�56 130 0�47 105 0�50 117 0�46 104
Table 3. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%) at
20 °C ambient temperature at the luminaire.
International
description TC-D
Socket G24Q1� G24Q2
Lamp power (W) 26 18 13 10
Luminous flux
ratio (%)
100 71 61 47 100 79 63 48 100 77 63 42 100 68 52
Switch setting 0 3 5 9 0 2 5 9 0 2 4 9 0 4 9
Number of
luminaires /
Current
consumption from
the battery /
Apparent power
[A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA]
1
0�36 85 0�28 63 0�27 61 0�27 64 0�30 51 0�26 37 0�24 29 0�23 24 0�26 60 0�26 49 0�21 49 0�21 49 0�25 58 0�21 49 0�20 44
2
0�39 93 0�35 80 0�33 76 0�47 87 0�35 64 0�29 47 0�28 37 0�39 90 0�30 68 0�28 63 0�29 66 0�39 90 0�26 58 0�26 62
3
0�54 126 0�45 104 0�36 80 0�65 114 0�48 86 0�36 65 0�32 48 0�53 121 0�41 91 0�32 73 0�30 71 0�54 125 0�31 74 0�30 70
4
0�57 132 0�43 97 0�60 106 0�44 81 0�34 62 0�53 110 0�38 87 0�32 74 0�38 88 0�32 72
5
0�71 125 0�53 94 0�40 73 0�57 130 0�48 103 0�33 76 0�47 104 0�36 75
6
0�60 108 0�44 83 0�52 120 0�38 87 0�54 121 0�40 81
7
0�59 136 0�42 94 0�59 137 0�45 94
Table 4. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%) at
20 °C ambient temperature at the luminaire.